Class C.
INSIDE WORK.
(Light, Power and Heat. For Signaling Systems, see Class E.)
All Systems and Voltages.
GENERAL RULES—ALL SYSTEMS AND VOLTAGES.
14. Wires—
(For special rules, see Nos. 18, 24, 32, 38 and 39.)
a. Must not be of smaller size than No. 14 B. & S., except as allowed under Rule 24 u and 40 c.
b. Tie wires must have an insulation equal to that of the conductors they confine.
c. Must be so spliced or joined as to be both mechanically and electrically secure without solder; they must then be soldered to insure preservation, and the joint covered with an insulation equal to that on the conductors. Stranded wires must be soldered before being fastened under clamps or binding screws, and, when they have a conductivity greater than that of No. 10 B. & S. copper wire, they must be soldered into lugs.
d. Must be separated from contact with walls, floors, timbers or partitions through which they may pass by non-combustible, non-absorptive insulating tubes, such as glass or porcelain.
e. Must be kept free from contact with gas, water or other metallic piping, or any other conductors or conducting material which they may cross, by some continuous and firmly fixed non-conductor, creating a separation of at least one inch. Deviations from this rule may sometimes be allowed by special permission.
f. Must be so placed in wet places that an air space will be left between conductors and pipes in crossing, and the former must be run in such a way that they cannot come in contact with the pipe accidentally. Wires should be run over, rather than under, pipes upon which moisture is likely to gather or which, by leaking, might cause trouble on a circuit.
15. Underground Conductors—
a. Must be protected, when brought into a building, against moisture and mechanical injury, and all combustible material must be kept removed from the immediate vicinity.
b. Must not be so arranged as to shunt the current through a building around any catch-box.
16. Table of Carrying Capacity of Wires—
Below is a table showing the allowable carrying capacity of wires containing ninety-eight per cent pure copper, which must be followed in placing interior conductors:
| Table A. | Table B. | |
|---|---|---|
| Rubber Covered Wires. | Weatherproof Wires. | |
| See No. 40 a. | See No. 40 b. | |
| B. & S. G. | Amperes. | Amperes. |
| 18 | 3 | 5 |
| 16 | 6 | 8 |
| 14 | 12 | 16 |
| 12 | 17 | 23 |
| 10 | 24 | 32 |
| 8 | 33 | 46 |
| 6 | 46 | 65 |
| 5 | 54 | 77 |
| 4 | 65 | 92 |
| 3 | 76 | 110 |
| 2 | 90 | 131 |
| 1 | 107 | 156 |
| 0 | 127 | 185 |
| 00 | 150 | 220 |
| 000 | 177 | 262 |
| 0000 | 210 | 312 |
| Circular Mils. | ||
| 200,000 | 200 | 300 |
| 300,000 | 270 | 400 |
| 400,000 | 330 | 500 |
| 500,000 | 390 | 590 |
| 600,000 | 450 | 680 |
| 700,000 | 500 | 760 |
| 800,000 | 550 | 840 |
| 900,000 | 600 | 920 |
| 1,000,000 | 650 | 1,000 |
| 1,100,000 | 690 | 1,080 |
| 1,200,000 | 730 | 1,150 |
| 1,300,000 | 770 | 1,220 |
| 1,400,000 | 810 | 1,290 |
| 1,500,000 | 850 | 1,360 |
| 1,600,000 | 890 | 1,430 |
| 1,700,000 | 930 | 1,490 |
| 1,800,000 | 970 | 1,550 |
| 1,900,000 | 1,010 | 1,610 |
| 2,000,000 | 1,050 | 1,670 |
17. Switches, Cut-outs, Circuit-Breakers, Etc.—
(For construction rules, see Nos. 43, 44 and 45.)
a. Must, whenever called for, unless otherwise provided (for exceptions, see No. 8 c and No. 22 c), be so arranged that the cut-outs will protect, and the opening of a switch or circuit breaker will disconnect, all of the wires; that is, in a two-wire system the two wires, and in a three-wire system the three wires, must be protected by the cut-out and disconnected by the operation of the switch or circuit-breaker.
b. Must not be placed in the immediate vicinity of easily ignitible stuff or where exposed to inflammable gases or dust or to flyings of combustible material.
c. Must, when exposed to dampness, either be inclosed in a waterproof box or mounted on porcelain knobs.
CONSTANT-CURRENT SYSTEMS.
PRINCIPALLY SERIES ARC LIGHTING.
18. Wires—
(See also Nos. 14, 15 and 16.)
a. Must have an approved rubber insulating covering. (see No. 40 a)
b. Must be arranged to enter and leave the building through an approved double-contact service switch (see No. 51 b), mounted in a non-combustible case, kept free from moisture, and easy of access to police or firemen.
c. Must always be in plain sight, and never encased, except when required by the Inspection Department having jurisdiction.
d. Must be supported on glass or porcelain insulators, which separate the wire at least one inch from the surface wired over, and must be kept rigidly at least eight inches from each other, except within the structure of lamps, on hanger-boards, in cut-out boxes, or like places, where a less distance is necessary.
e. Must, on side walls, be protected from mechanical injury by a substantial boxing, retaining an air space of one inch around the conductors, closed at the top (the wires passing through bushed holes), and extending not less than seven feet from the floor. When crossing floor timbers in cellars, or in rooms where they might be exposed to injury, wires must be attached by their insulating supports to the under side of a wooden strip not less than one-half an inch in thickness.
19. Arc Lamps—
(For construction rules, see No. 57.)
a. Must be carefully isolated from inflammable material.
b. Must be provided at all times with a glass globe surrounding the arc, securely fastened upon a closed base. No broken or cracked globes to be used.
c. Must be provided with a wire netting (having a mesh not exceeding one and one-quarter inches) around the globe, and an approved spark arrester (see No. 50), when readily inflammable material is in the vicinity of the lamps, to prevent escape of sparks, melted copper or carbon. It is recommended that plain carbons, not copper-plated, be used for lamps in such places.
d. Where hanger-boards (see No. 48) are not used, lamps must be hung from insulating supports other than their conductors.
20. Incandescent Lamps in Series Circuits—
a. Must have the conductors installed as provided in Rule No. 18, and each lamp must be provided with an automatic cut-out.
b. Must have each lamp suspended from a hanger-board by means of rigid tube.
c. No electro-magnetic device for switches and no system of multiple-series or series-multiple lighting will be approved.
d. Under no circumstances can they be attached to gas fixtures.
CONSTANT-POTENTIAL SYSTEMS.
GENERAL RULES—ALL VOLTAGES.
21. Automatic Cut-outs (Fuses and Circuit-Breakers.)
(See No. 17, and for construction, Nos. 44 and 45.)
a. Must be placed on all service wires, either overhead or underground, as near as possible to the point where they enter the building and inside the walls, and arranged to cut off the entire current from the building.
b. Must be placed at every point where a change is made in the size of wire [unless the cut-out in the larger wire will protect the smaller. (See No. 16)].
c. Must be in plain sight, or inclosed in an approved box (see No. 46), and readily accessible. They must not be placed in the canopies or shells of fixtures.
d. Must be so placed that no set of incandescent lamps, whether grouped on one fixture or several fixtures or pendants, requiring a current of more than six amperes shall be dependent upon one cut-out. Special permission may be given in writing by the Inspection Department having jurisdiction for departure from this rule in the case of large chandeliers.
e. Must be provided with fuses, the rated capacity of which does not exceed the allowable carrying capacity of the wire, and, when circuit breakers are used, they must not be set more than about thirty per cent above the allowable carrying capacity of the wire, unless a fusible cut-out is also installed in the circuit (see No. 16).
22. Switches—
(See No. 17, and for construction, No. 43.)
a. Must be placed on all service wires, either overhead or underground, in a readily accessible place, as near as possible to the point where the wires enter the building, and arranged to cut off the entire current.
b. Must always be placed in dry, accessible places, and be grouped as far as possible. Knife switches must be so placed that gravity will tend to open rather than close the switch.
c. Must not be single-pole, except when the circuits which they control supply not more than six 16 candle-power lamps or their equivalent.
d. Where gangs of flush switches are used, whether with conduit systems or not, the switches must be inclosed in boxes constructed of or lined with fire resisting material. Where two or more switches are placed under one plate, the box must have a separate compartment for each switch. No push buttons for bells, gas lighting circuits or the like shall be placed in the same wall plate with switches controlling electric light or power wiring.
23. Electric Heaters—
a. Must, if stationary, be placed in a safe situation, isolated from inflammable materials and be treated as sources of, heat.
b. Must each have a cut-out and indicating switch (see No. 17 a).
c. Must have the attachments of feed wires to the heaters in plain sight, easily accessible and protected from interference, accidental or otherwise.
c. Flexible conductors for smoothing irons and sad irons, and for all devices requiring over 250 watts, must comply with Rule 45, section g.
d. The flexible conductors for portable apparatus, such as irons, etc., must have an approved insulating covering (see No. 40 c, 3).
e. Must each be provided with name plate, giving the maker's name and the normal capacity in volts and amperes.
LOW-POTENTIAL SYSTEMS.
300 VOLTS OR LESS.
Any circuit attached to any machine, or combination of machines, which develops a difference of potential between any two wires, of over ten volts and less than 300 volts, shall be considered as a low-potential circuit, and as coming under the class, unless an approved transforming device is used, which cuts the difference of potential down to ten volts or less. The primary circuit not to exceed a potential of 3,000 volts.
24. Wires—
GENERAL RULES.
(See also Nos. 14, 15, and 16.)
a. Must not be laid in plaster, cement, or similar finish.
b. Must never be fastened with staples.
c. Must not be fished for any great distance, and only in places where the inspector can satisfy himself that the rules have been complied with.
d. Twin wires must never be used, except in conduits, or where flexible conductors are necessary.
e. Must be protected on side walls from mechanical injury. When crossing floor timbers in cellars or in rooms, where they might be exposed to injury, wires must be attached by their insulating supports to the under side of a wooden strip, not less than one-half inch in thickness, and not less than three inches in width.
f. When run immediately under roofs, or in proximity to water tanks or pipes, will be considered as exposed to moisture.
SPECIAL RULES.
For open work:
In Dry Places:
g. Must have an approved rubber or weatherproof insulation (See No. 40 a and b.)
h. Must be rigidly supported on non-combustible, non-absorptive insulators, which separate the wire at least one-half inch from the surface wired over, and they must be kept apart at least two and one-half inches.
In damp places, such as Breweries, Packing Houses, Stables, Dye Houses, Paper or Pulp Mills, or building specially liable to moisture or acid or other fumes liable to injure the wires or their insulation, except where used for pendants:
i. Must have an approved rubber insulating covering (see No. 40 a).
j. Must be rigidly supported on non-combustible, non-absorptive insulators, which separate the wire at least one inch from the surface wired over, and must be kept apart at least two and one-half inches.
k. Must have no joints or splices.
For moulding work:
l. Must have approved rubber insulating covering (see No. 40 a).
m. Must never be placed in moulding in concealed or damp places.
For conduit work:
n. Must have an approved rubber insulating covering (see No. 40 e).
o. Must not be drawn in until all mechanical work on the building has been, as far as possible, completed.
p. Must not have wires of different circuits drawn in the same conduit.
q. Must, for alternating systems, have the two or more wires of a circuit drawn in the same conduit.
For so-called concealed work:
r. Must have an approved rubber insulating covering (see No. 40 a).
s. Must be rigidly supported on non-combustible, non-absorptive insulators which separate the wire at least one inch from the surface wired over, and must be kept at least ten inches apart, and, when possible, should be run singly on separate timbers or studding.
t. When from the nature of the case it is impossible to place concealed wiring on non-combustible insulating supports of glass or porcelain, the wires, if not exposed to moisture, may be fished on the loop system if incased throughout in approved continuous flexible tubing or conduit. (See page 45.)
For fixture work:
u. Must have an approved rubber insulating covering (see No. 40 d), and shall not be less in size than No. 18 B. & S.
v. Supply conductors, and especially the splices to fixture wires, must be kept clear of the grounded part of gas pipes, and, where shells are used, the latter must be constructed in a manner affording sufficient area to allow this requirement.
w. Must, when fixtures are wired outside, be so secured as not to be cut or abraded by the pressure of the fastenings or motion of the fixture.
25. Interior Conduits—
(See also Nos. 24 n to q, and 41.)
a. Must be continuous from one junction box to another or to fixtures, and the conduit tube must properly enter all fittings.
b. Must be first installed as a complete conduit system, without the conductors.
c. Conduits must extend at least one-half inch beyond the finished surface of walls or ceilings, except that, if the end is threaded and a coupling screwed on, the conduit may be left flush with the surface, and the coupling may be removed when work on building is completed.
d. Must, after conductors are introduced, have all outlets plugged with special wood or fibrous plugs, made in parts, and the outlet then sealed with approved compound. Joints must be made airtight and moisture proof.
e. Must have the metal of the conduit permanently and effectually grounded.
26. Fixtures—
(See also No. 24 u to w.]
a. Must, when supported from the gas piping of a building, be insulated from the gas piping of a building, be insulated from the gas-pipe system by means of approved insulating joints (see No. 51) placed as close as possible to the ceiling.
b. Must have all burs, or fins, removed before the conductors are drawn into the fixture.
c. The tendency to condensation within the pipes should be guarded against by sealing the upper end of the fixture.
d. No combination fixture in which the conductors are concealed in a space less than one-fourth inch between the inside pipe and the outside casing will be approved.
e. Must be tested for "contacts" between conductors and fixtures, for "short circuits" and for ground connections before it is connected to its supply conductors.
f. Ceiling blocks of fixtures should be made of insulating material; if not, the wires in passing through the plate must be surrounded with non-combustible, non-absorptive, insulating material, such as glass or porcelain.
27. Sockets—
(For construction rules, see No. 47.)
a. In rooms where inflammable gases may exist the incandescent lamp and socket must be inclosed in a vapor-tight globe, and supported on a pipe-hanger, wired with approved rubber-covered wire (see No. 40 a) soldered directly to the circuit.
b. In damp or wet places, or over specially inflammable stuff, waterproof sockets must be used.
28. Flexible Cord—
a. Must have an approved insulation and covering (see No. 40 c.)
b. Must not be used as a support for clusters.
c. Must not be used except for pendants, wiring of fixtures and portable lamps or motors.
d. Must not be used in show windows.
e. Must be protected by insulating bushings where the cord enters the socket.
f. Must be so suspended that the entire weight of the socket and lamp will be borne by knots under the bushing in the socket, and above the point where the cord comes through the ceiling block or rosette, in order that the strain may be taken from the joints and binding screws.
29. Arc Lamps on Constant-Potential Circuits—
a. Must have a cut-out (see No. 17 a) for each lamp or each series of lamps.
b. Must only be furnished with such resistances or regulators as are inclosed in non-combustible material, such resistances being treated as sources of heat. Incandescent lamps must not be used for resistance devices.
c. Must be supplied with globes and protected by spark arresters and wire netting around the globe, as in the case of arc lamps on high-potential circuits. (see Nos. 19 and 50).
30. Economy Coils—
a. Economy and compensator coils for arc lamps must be mounted on non-combustible, non-absorptive insulating supports, such as glass or porcelain, allowing an air space of at least one inch between frame and support, and in general to be treated like sources of heat.
31. Decorative Series Lamps—
a. Incandescent lamps run in series shall not be used for decorative purposes inside of buildings, except by special permission in writing from the Inspection Department having jurisdiction.
HIGH-POTENTIAL SYSTEMS.
300 To 3,000 Volts.
Any circuit attached to any machine or combination of machines, which develops a difference of potential, between any two wires, of over 300 volts and less than 3,000 volts, shall be considered as a high potential circuit, and as coming under that class, unless an approved transforming device is used, which cuts the difference of potential down to 300 volts or less.
32. Wires—
(See also Nos. 14, 15 and 16.)
a. Must have an approved rubber-insulating covering. (See No. 40 a.)
b. Must be always in plain sight and never incased, except where required by the Inspection Department having jurisdiction.
c. Must be rigidly supported on glass or porcelain insulators, which raise the wire at least one inch from the surface wired over, and must be kept apart at least four inches for voltages up to 750 and at least eight inches for voltages over 750.
d. Must be protected on side walls from mechanical injury by a substantial boxing, retaining an air space of one inch around the conductors, closed at the top (the wires passing through bushed holes) and extending not less than seven feet from the floor. When crossing floor timbers, in cellars, or in rooms, where they might be exposed to injury, wires must be attached by their insulating supports to the under side of a wooden strip not less than one-half an inch in thickness.
33. Transformers (When permitted inside buildings, see No. 13)—
(For construction rules, see No. 54.)
a. Must be located at a point as near as possible to that at which the primary wires enter the building.
b. Must be placed in an inclosure constructed of or lined with fire-resisting material; the inclosure to be used only for this purpose, and to be kept securely locked, and access to the same allowed only to responsible parties.
c. Must be effectually insulated from the ground and the inclosure in which they are placed must be practically air tight, except that it shall be thoroughly ventilated to the outdoor air, if possible, through a chimney or flue. There should be at least six inches air space on all sides of the transformer.
34. Car Wiring—
a. Must be always run out of reach of the passengers, and must have an approved rubber insulating covering. (See No. 40 a.)
35. Car Houses—
a. Must have the trolley wires securely supported on insulating hangers.
b. Must have the trolley hangers placed at such a distance apart that, in case of a break in the trolley wire, contact can not be made with the floor.
c. Must have cut-out switch located at a proper place outside of the building, so that all trolley circuits in the building can be cut out at one point, and line circuit breakers must be installed, so that when this cut-out switch is open the trolley wire will be dead at all points within 100 feet of the building. The current must be cut out of the building whenever the same is not in use or the road is not in operation.
d. Must have all lamps and stationary motors installed in such a way that one main switch can control the whole of each installation—lighting or power—independently of main feeder-switch. No portable incandescent lamps or twin wire allowed, except that portable incandescent lamps may be used in the pits, connections to be made by two approved rubber-covered flexible wires (see No. 40 a), properly protected against mechanical injury; the circuit to be controlled by a switch placed outside of the pit.
e. Must have all wiring and apparatus installed in accordance with rules under Class "C" for constant potential systems.
f. Must not have any system of feeder distribution centering in the building.
g. Must have the rails bonded at each joint with not less than No. 2 B. & S. annealed copper wire; also a supplementary wire to be run for each track.
h. Must not have cars left with trolley in electrical connection with the trolley wire.
36. Lighting and Power from Railway Wires—
a. Must not be permitted, under any pretense, in the same circuit with trolley wires with a ground return, except in electric railway cars, electric car houses, and their power stations, nor shall the same dynamo be used for both purposes.
37. Series Lamps—
a. No system of multiple-series or series-multiple for light or power will be approved.
b. Under no circumstances can lamps be attached to gas fixtures.
EXTRA-HIGH-POTENTIAL SYSTEMS.
OVER 3,500 VOLTS.
Any circuit attached to any machine or combination of machines, which develops a difference of potential, between any two wires, of over 3,000 volts, shall be considered as an extra high potential circuit, and as coming under that class, unless an approved transforming device is used, which cuts the difference of potential down to 3,000 volts or less.
38. Primary Wires—
Must not be brought into or over buildings, except power stations and sub-stations.
39. Secondary Wires—
a. Must be installed under Rules for high-potential systems when their immediate primary wires carry a current at a potential of over 3,000 volts.